需求概述
本章要實現一個流程:EG8200采集西門子S7-200Smart的數據,并組裝成JSON格式通過HTTP上報應用平臺。
源-(S7轉Modbus-https://www.iotrouter.com/news/2150.html)
要采集的PLC點位表如下:
| PLC | S7-200 Smart | ||
| IP | 192.168.0.34/102 | ||
| 點表(DB1) | |||
| 地址 | 數據類型 | 屬性 | 名稱 |
| V0.0 | Boolean | 只讀 | 風機1接觸器異常 |
| V0.6 | Boolean | 只讀 | 風機2接觸器異常 |
| V1.6 | Boolean | 只讀 | 風機3接觸器異常 |
| V2.5 | Boolean | 只讀 | 變頻器通訊故障 |
| I0.0 | Boolean | 只讀 | 電機高溫報警 |
| I0.1 | Boolean | 只讀 | 溫度狀態異常 |
| VD4 | Float | 只讀 | 油壓工程值 |
| VD8 | Float | 只讀 | 吸入壓力工程值 |
| VD12 | Float | 只讀 | 燃油油位工程值 |
| VD16 | Float | 只讀 | 機柜溫度值 |
| VD20 | Float | 只讀 | 發動機電壓值 |
| VD24 | Float | 只讀 | 發動機電流值 |
| VD28 | Float | 只讀 | 發動機工作時間 |
| VD32 | Float | 只讀 | 泵壓工程值 |
| VW120 | Unsigned16 | 只讀 | 本機編號 |
| VW750 | Unsigned16 | 只讀 | 本機組號 |
| VW2402 | Unsigned16 | 只讀 | 電機1溫度 |
| VW2404 | Unsigned16 | 只讀 | 電機2溫度 |
| VW2406 | Unsigned16 | 只讀 | 電機3溫度 |
| VW2408 | Unsigned16 | 只讀 | 風機1溫度 |
| VW2410 | Unsigned16 | 只讀 | 風機2溫度 |
| VW2412 | Unsigned16 | 只讀 | 風機3溫度 |
HTTP通信相關參數格式如下:
##數據推送 url:192.168.0.32:1880/api/device/reportData method:POST JSON格式: { "deviceInfo": { "machineNumber": 9301, "machineGroupNumber": 1 }, "status": { "fan1ContactError": true, "fan2ContactError": false, "fan3ContactError": false, "inverterCommError": false, "motorHighTempAlarm": false, "temperatureStatusError": false }, "data": { "oilPressure": 17.83, "suctionPressure": 3.7, "fuelLevel": 0.23, "cabinetTemperature": 237.2, "engineVoltage": 415.64, "engineCurrent": 65.1, "engineRuntime": 72.6, "pumpPressure": 85.3, "motor1Temperature": 20, "motor2Temperature": 19, "motor3Temperature": 19, "fan1Temperature": 21, "fan2Temperature": 33, "fan3Temperature": 26 }, "timestamp": "2022-7-08 11:28:55" }
需求分析
在制作流程時,基礎的邏輯是根據數據走向來制作流程。其中主要工作分為三步:
第一步:通過S7協議讀取PLC變量數據,得到的數據存儲在內存中(西門子節點)
第二步:將數據按照JSON格式進行格式化(函數節點)
第三步:配置HTTP 請求參數

需求實現
1. 采集PLC數據
從節點庫拖入一個西門子節點,以及一個調試節點,調試節點用于查看讀取到的PLC數據集,方便定位問

雙擊西門子節點,根據需求概述的內容填寫對應的設置參數,如下圖所示:
IP:PLC的IP 端口:102(S7協議通信默認端口102) 采集周期:1000ms(默認2000ms,可自定義) 超時周期:2000ms(默認2000ms,可自定義) 數據點配置(根據幫助文檔可以找到對應關系) V0.0 V0.6 V1.6 V2.5 I0.0 I0.1 VD4 VD8 VD12 VD16 VD20 VD24 VD28 VD32 VW120 VW750 VW2402 VW2404 VW2408 VW2410 VW2412 如果是連續地址,可配置起始地址并填寫讀取長度即可
如果設置正確,調試窗口會有日志打印,顯示的是讀取到的數據內容:

有的時候PLC數據點比較多,手動依次錄入比較繁瑣。節點支持數據點的導入導出或者參數傳遞的方式來讀取:

本例程用到的傳參方案,函數節點內的代碼如下:
msg.payload = [ { func: "ReadBoolArray", body: { name: "", address: "V0", length: 8 } }, { func: "ReadBoolArray", body: { name: "", address: "V1", length: 8 } }, { func: "ReadBoolArray", body: { name: "", address: "V2", length: 8 } }, { func: "ReadFloatArray", body: { name: "", address: "VD4", length: 8 } }, { func: "ReadUInt16", body: { name: "", address: "VW120" } }, { func: "ReadUInt16", body: { name: "", address: "VW750" } }, { func: "ReadUInt16Array", body: { name: "", address: "VW2402", length: 6 } }, { func: "ReadBoolArray", body: { name: "", address: "I0", length: 8 } } ] return msg;
2. 數據格式化
根據步驟引導,在調試窗口可以看到讀到的PLC數據如下:

因為應用平臺已經規定了數據必須按照JSON格式上報。接下來使用函數節點Javascrip代碼將數據進行格式化,代碼如下:
class DeviceReport {
constructor(machineNumber, machineGroupNumber) {
this.deviceInfo = {
machineNumber: machineNumber,
machineGroupNumber: machineGroupNumber
};
this.status = {
fan1ContactError: 0,
fan2ContactError: 0,
fan3ContactError: 0,
inverterCommError: 0,
motorHighTempAlarm: 0,
temperatureStatusError: 0
};
this.data = {
oilPressure: 0,
suctionPressure: 0,
fuelLevel: 0,
cabinetTemperature: 0,
engineVoltage: 0,
engineCurrent: 0,
engineRuntime: 0,
pumpPressure: 0,
motor1Temperature: 0,
motor2Temperature: 0,
motor3Temperature: 0,
fan1Temperature: 0,
fan2Temperature: 0,
fan3Temperature: 0
};
this.timestamp = null;
}
// 設置狀態數據(1表示異常,0表示正常)
setStatusData(statusData) {
this.status = statusData;
}
// 設置傳感器數據
setSensorData(sensorData) {
this.data = sensorData;
}
// 設置時間戳
setTimestamp(timestamp) {
this.timestamp = timestamp;
}
generateReport() {
return {
deviceInfo: this.deviceInfo,
status: this.status,
data: this.data,
timestamp: this.timestamp
};
}
}
function dateFormat(fmt, timestamp) {
let ret;
const opt = {
"Y+": timestamp.getFullYear().toString(), // 年
"m+": (timestamp.getMonth() + 1).toString(), // 月
"d+": timestamp.getDate().toString(), // 日
"H+": timestamp.getHours().toString(), // 時
"M+": timestamp.getMinutes().toString(), // 分
"S+": timestamp.getSeconds().toString() // 秒
};
for (let k in opt) {
ret = new RegExp("(" + k + ")").exec(fmt);
if (ret) {
fmt = fmt.replace(ret[1], (ret[1].length == 1) ? (opt[k]) : (opt[k].padStart(ret[1].length, "0")))
};
};
return fmt;
}
function setValue(data) {
var myDeviceReport = new DeviceReport(data.VW120, data.VW750)
var v0 = data.V0
var v1 = data.V1
var v2 = data.V2
var i0 = data.I0
var vd4 = data.VD4
var vd2402 = data.VW2402
const fmt = dateFormat("YYYY-mm-dd HH:MM:SS", new Date())
try {
// 設置狀態數據
const statusData = {
fan1ContactError: v0[0],
fan2ContactError: v0[6],
fan3ContactError: v1[6],
inverterCommError: v2[5],
motorHighTempAlarm: i0[0],
temperatureStatusError: i0[1]
}
myDeviceReport.setStatusData(statusData)
// 設置傳感器數據
const sensorData = {
oilPressure: vd4[0],
suctionPressure: vd4[1],
fuelLevel: vd4[2],
cabinetTemperature: vd4[3],
engineVoltage: vd4[4],
engineCurrent: vd4[5],
engineRuntime: vd4[6],
pumpPressure: vd4[7],
motor1Temperature: vd2402[0],
motor2Temperature: vd2402[1],
motor3Temperature: vd2402[2],
fan1Temperature: vd2402[3],
fan2Temperature: vd2402[4],
fan3Temperature: vd2402[5]
}
myDeviceReport.setSensorData(sensorData)
// 設置時間戳
myDeviceReport.setTimestamp(fmt)
//生成JSON對象返回
return myDeviceReport.generateReport()
} catch (err) {
node.error(err.message);
return null
}
}
var plcData = msg.payload
if (setValue(plcData)){
msg.payload = JSON.stringify(setValue(plcData),null,2)
return msg
}
復制以上代碼,粘貼到函數節點內,部署后即可看到效果:

可以看到,已經將讀到的PLC數據,按照需求要求轉換成了最終的JSON格式,且對數據進行了一定程度的計算(兩位小數)。此處只是函數節點的冰山一角,因為支持Javascrip語言編程,幾乎你能想到的任何功能都可以在這里實現。
3. 通過http周期上報
拖入一個HTTP節點,根據提示進行配置地址和請求方式,即可實現數據上報:

服務端返回成功,至此,數據上報已經完成,很簡單幾步即可實現:采集PLC數據并按照自定義JSON格式上報。
源碼
所有的流程支持以json格式導入導出,方便與其他人分享做好的流程。本章節的流程json文件如下,復制后在菜單欄右上角選擇導入粘貼即可,導出同理
[{"id":"edf0c4c538469caa","type":"Siemens","z":"5bb1b94e3403e2f2","name":"","protocol":"iplink_SiemensS7","IPAddress":"192.168.0.34","DestPort":"102","IPLinkTimeout":"2000","IPCommTimeout":"2000","Spname":"COM10","Baudrate":"9600","Databits":"8","Stopbit":"1","Paritybit":"0","RTSEnable":false,"SpLinktimeout":"2000","SpIntertimeout":"-1","workMode":"read","readMode":"trigger","readCyc":"1000","vartable":[],"SiemensS7Model":"5","SiemensS7ConnectionType":"1","SiemensS7Rack":"0","SiemensS7Slot":"0","SiemensS7LocalTSAP":"102","SiemensS7DestTSAP":"4D57","SiemensPPIStation":"2","stringvar":[],"customName":"Siemens:S7-S200Smart","x":510,"y":1080,"wires":[["be890e0383a04306"]]},{"id":"90be80aa485c48ae","type":"debug","z":"5bb1b94e3403e2f2","name":"調試 22","active":true,"tosidebar":true,"console":false,"tostatus":false,"complete":"false","statusVal":"","statusType":"auto","x":1020,"y":1080,"wires":[]},{"id":"2485d94e74e61614","type":"function","z":"5bb1b94e3403e2f2","name":"函數計算 18","func":"msg.payload = [n { func: "ReadBoolArray", body: { name: "", address: "V0", length: 8 } },n { func: "ReadBoolArray", body: { name: "", address: "V1", length: 8 } },n { func: "ReadBoolArray", body: { name: "", address: "V2", length: 8 } },n { func: "ReadFloatArray", body: { name: "", address: "VD4", length: 8 } },n { func: "ReadUInt16", body: { name: "", address: "VW120" } },n { func: "ReadUInt16", body: { name: "", address: "VW750" } },n { func: "ReadUInt16Array", body: { name: "", address: "VW2402", length: 6 } },n { func: "ReadBoolArray", body: { name: "", address: "I0", length: 8 } }n]nreturn msg;","outputs":1,"noerr":0,"initialize":"","finalize":"","libs":[],"x":310,"y":1080,"wires":[["edf0c4c538469caa"]]},{"id":"8db3c718ecac3ed7","type":"inject","z":"5bb1b94e3403e2f2","name":"","props":[{"p":"payload"},{"p":"topic","vt":"str"}],"repeat":"","crontab":"","once":false,"onceDelay":0.1,"topic":"","payload":"","payloadType":"date","x":150,"y":1080,"wires":[["2485d94e74e61614"]]},{"id":"be890e0383a04306","type":"function","z":"5bb1b94e3403e2f2","name":"函數計算 19","func":"class DeviceReport {n constructor(machineNumber, machineGroupNumber) {n this.deviceInfo = {n machineNumber: machineNumber,n machineGroupNumber: machineGroupNumbern };n this.status = {n fan1ContactError: 0,n fan2ContactError: 0,n fan3ContactError: 0,n inverterCommError: 0,n motorHighTempAlarm: 0,n temperatureStatusError: 0n };n this.data = {n oilPressure: 0,n suctionPressure: 0,n fuelLevel: 0,n cabinetTemperature: 0,n engineVoltage: 0,n engineCurrent: 0,n engineRuntime: 0,n pumpPressure: 0,n motor1Temperature: 0,n motor2Temperature: 0,n motor3Temperature: 0,n fan1Temperature: 0,n fan2Temperature: 0,n fan3Temperature: 0n };n this.timestamp = null;n }nn // 設置狀態數據(1表示異常,0表示正常)n setStatusData(statusData) {n this.status = statusData;n }nn // 設置傳感器數據n setSensorData(sensorData) {n this.data = sensorData;n }nn // 設置時間戳n setTimestamp(timestamp) {n this.timestamp = timestamp;n }n generateReport() {n return {n deviceInfo: this.deviceInfo,n status: this.status,n data: this.data,n timestamp: this.timestampn };n }n}nnfunction dateFormat(fmt, timestamp) {n let ret;n const opt = {n "Y+": timestamp.getFullYear().toString(), // 年n "m+": (timestamp.getMonth() + 1).toString(), // 月n "d+": timestamp.getDate().toString(), // 日n "H+": timestamp.getHours().toString(), // 時n "M+": timestamp.getMinutes().toString(), // 分n "S+": timestamp.getSeconds().toString() // 秒n };n for (let k in opt) {n ret = new RegExp("(" + k + ")").exec(fmt);n if (ret) {n fmt = fmt.replace(ret[1], (ret[1].length == 1) ? (opt[k]) : (opt[k].padStart(ret[1].length, "0")))n };n };n return fmt;n}nfunction setValue(data) {n var myDeviceReport = new DeviceReport(data.VW120, data.VW750)n var v0 = data.V0n var v1 = data.V1n var v2 = data.V2n var i0 = data.I0n var vd4 = data.VD4n var vd2402 = data.VW2402n const fmt = dateFormat("YYYY-mm-dd HH:MM:SS", new Date())n try {n // 設置狀態數據n const statusData = {n fan1ContactError: v0[0],n fan2ContactError: v0[6],n fan3ContactError: v1[6],n inverterCommError: v2[5],n motorHighTempAlarm: i0[0],n temperatureStatusError: i0[1]n }n myDeviceReport.setStatusData(statusData)nn // 設置傳感器數據n const sensorData = {n oilPressure: vd4[0],n suctionPressure: vd4[1],n fuelLevel: vd4[2],n cabinetTemperature: vd4[3],n engineVoltage: vd4[4],n engineCurrent: vd4[5],n engineRuntime: vd4[6],n pumpPressure: vd4[7],n motor1Temperature: vd2402[0],n motor2Temperature: vd2402[1],n motor3Temperature: vd2402[2],n fan1Temperature: vd2402[3],n fan2Temperature: vd2402[4],n fan3Temperature: vd2402[5]n }n myDeviceReport.setSensorData(sensorData)n // 設置時間戳n myDeviceReport.setTimestamp(fmt)n //生成JSON對象返回n return myDeviceReport.generateReport()n } catch (err) {n node.error(err.message);n return nulln }nn}nvar plcData = msg.payloadnif (setValue(plcData)) {n msg.payload = JSON.stringify(setValue(plcData), null, 2)n return msgn}n","outputs":1,"noerr":0,"initialize":"","finalize":"","libs":[],"x":710,"y":1080,"wires":[["d140dc012c0cd68f"]]},{"id":"d140dc012c0cd68f","type":"http request","z":"5bb1b94e3403e2f2","name":"","method":"POST","ret":"txt","paytoqs":"ignore","url":"192.168.0.32:1880/api/device/reportData","tls":"","persist":false,"proxy":"","insecureHTTPParser":false,"authType":"","senderr":false,"headers":[],"x":860,"y":1080,"wires":[["90be80aa485c48ae"]]}]
審核編輯 黃宇
-
西門子
+關注
關注
98文章
3312瀏覽量
120382 -
HTTP
+關注
關注
0文章
537瀏覽量
35359 -
邊緣計算
+關注
關注
22文章
3527瀏覽量
53449
發布評論請先 登錄
西門子S7-1200/1500 PLC數據采集上云實戰指南
無需更換PLC!讓西門子S7-1200輕松驅動匯川EtherCAT伺服
鋇錸技術BL118 Node-Red邊緣計算網關西門子PLC S7協議使用方法
風電場智能化管控:EtherCAT轉ProfiNet協議助力貝加萊X20CP3586與西門子S7-1500協同
承擔CANOPEN轉PROFINET協議轉換功能的網關與臺達伺服器的連接
Profibus DP轉DeviceNet實現西門子S7–300與羅克韋爾PLC在汽車制造車間的跨協議協同控制案例
ProfibusDP轉DeviceNet施耐德PLC聯合西門子S7–1200提升物流倉儲貨物分揀效率技術案例
西門子PLC(S7-1200/1500/300/400)的數據采集與監控方案
CANopen轉PROFINET網關:西門子S7-1200 PLC與歐姆龍NJ系列PLC通信方案
如何破解三菱PLC與西門子PLC的通訊難題
Profinet轉DeviceNet網關協議轉換的技術實現與應用分析
工業智能網關可以采集西門子PLC嗎
西門子S7 PLC通過深控技術無點表工業網關實現數據采集與智能決策方案
MCGS觸摸屏與西門子S7系列PLC以太網通信
Profinet轉EtherCAT深度解讀網關模塊如何協議轉換賦能西門子PLC與伺服驅動高效協作案例?
教程-西門子S7協議轉換為HTTP協議
評論