KCD2-SCD-EX1安全柵現貨直發
型號:
KCD2-SCD-EX1
| General specifications | ||
|---|---|---|
| Signal type | Analog output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | 19 ... 30 V DC | |
| Ripple | ≤ 10 % | |
| Rated current | ≤ 33 mA at 24 V | |
| Power dissipation | ≤ 700 mW at 20 mA and 500 Ω load | |
| Power consumption | ≤ 800 mW | |
| Input | ||
| Connection side | control side | |
| Connection | terminals 5-, 6+ | |
| Input signal | 4 ... 20 mA , limited to approx. 25 mA | |
| Input voltage | open loop voltage of the control system < 60 V | |
| Voltage drop | approx. 6 V at 20 mA | |
| Input resistance | > 100 kΩ, with field wiring open or < 50 Ω | |
| Output | ||
| Connection side | field side | |
| Connection | terminals 1+, 2- | |
| Voltage | ≥ 13 V at 20 mA | |
| Current | 4 ... 20 mA | |
| Load | 100 ... 650 Ω | |
| Ripple | 20 mV rms | |
| Line fault detection | field wiring open or < 50 Ω and test current < 2 mA | |
| Transfer characteristics | ||
| Deviation | at 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis | |
| Influence of ambient temperature | < 2 μA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 μA/K (-40 ... -20 °C (-40 ... -4 °F)) | |
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB) | |
| Rise time | 10 to 90 % ≤ 10 ms | |
| Galvanic isolation | ||
| Input/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 | |
| Degree of protection | IEC 60529 | |
| Protection against electrical shock | UL 61010-1:2012 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-type examination certificate | CESI 20 ATEX 016 X | |
| Marking | ![]() II (1)G [Ex ia Ga] IIC ![]() II (1)D [Ex ia Da] IIIC ![]() I (M1) [Ex ia Ma] I | |
| Output | Ex ia | |
| Supply | ||
| Maximum safe voltage | 250 V AC (Attention! Um is no rated voltage.) | |
| Equipment | terminals 1+, 2- | |
| Voltage Uo | 25.2 V | |
| Current Io | 100 mA | |
| Power Po | 630 mW | |
| Internal capacitance Ci | 5.7 nF | |
| Internal inductance Li | negligible | |
| Certificate | CESI 20 ATEX 017 X | |
| Marking | ![]() II 3G Ex ec IIC T4 Gc | |
| Galvanic isolation | ||
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-11:2012 , EN 60079-7:2015 | |