安全柵KFD2-SCD-EX1.LK 現貨直發
型號:
KFD2-SCD-EX1.LK
| General specifications | ||
|---|---|---|
| Signal type | Analog output | |
| Supply | ||
| Connection | Power Rail or terminals 11+, 12- | |
| Rated voltage | 20 ... 35 V DC | |
| Ripple | within the supply tolerance | |
| Power dissipation | 1.1 W at 20 mA into 10 V (equivalent to 500 Ω) load | |
| Power consumption | 1.3 W | |
| Input | ||
| Connection | terminals 7-, 8+ | |
| Voltage drop | approx. 4 V or internal resistance 200 Ω at 20 mA | |
| Input resistance | > 100 kΩ, when wiring resistance in the field < 50 Ω or > 800 Ω at 20 mA | |
| Current | 4 ... 20 mA limited to approx. 25 mA | |
| Output | ||
| Connection | terminals 1+, 2- | |
| Current | 4 ... 20 mA | |
| Load | 100 ... 700 Ω | |
| Voltage | ≥ 14 V at 20 mA | |
| Transfer characteristics | ||
| Rise time | < 100 μs at bounce from 10 ... 90 % | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2004/108/EC | EN 61326-1:2006 | |
| Conformity | ||
| Insulation coordination | EN 50178:1997 | |
| Galvanic isolation | EN 50178:1997 | |
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 115 x 115 mm (0.8 x 4.5 x 4.5 inch) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | BAS 00 ATEX 7215 , for additional certificates see www.pepperl-fuchs.com | |
| Group, category, type of protection | ![]() II (1)GD [EEx ia] IIC (-20 °C ≤ Tamb ≤ 60 °C) | |
| Statement of conformity | TüV 99 ATEX 1499 X , observe statement of conformity | |
| Group, category, type of protection, temperature class | ![]() II 3G Ex nA II T4 [device in zone 2] | |
| Directive conformity | ||
| Directive 94/9/EC | EN 50014, EN 50020, EN 50021, EN 60079-0, EN 60079-15 | |